1/4 HSS5X3X1/4 LSH NOTE: *MULTIPLE HSS BEAMS MAY CANTILEVER OFF THE SAME COLUMN IN DIFFERENT DIRECTIONS. FOR THESE CONDITIONS, MAX HOR DIMENSION TO BE 2'-0" REF PLAN FOR HSS CANTILEVER BEAM LOCATIONS FUEL PIPING MAX DESIGN 20 PLF REF MECH HSS6X6X5/16 COLUMN RE: PLAN CL DETAIL A 1/4" THICK CAP PLATE T/STL VARIES REF MECH 1/2" NOTES: 1. GC SHALL VERIFY REQUIRED TOP OF STEEL WITH MECHANICAL CONTRACTOR BEFORE SHOP DRAWINGS ARE STARTED. 2. PRIOR TO FOUNDATION CONSTRUCTION, GC AND FOUNDATION CONTRACTOR TO COORDINATE EXACT LOCATIONS OF FUEL LINE PIPES, TO LOCATE THE TRESTLE SUPPORTS AND FOUNDATIONS. WHAT IS PROVIDED IN THE FOUNDATION DRAWINGS IS BASED ON LOCATIONS PROVIDED AS PART OF THE BASIS OF DESIGN 3. SEAL ALL ENDS OF HSS MEMBERS TO PREVENT WATER LEAKS. 3'-6" MAX*