CHANNEL SPAN 4' - 0" MAX. LADDER TRAY 1/2" Ø THREADED ROD, USE 5/8" Ø ROD AT THREE TIER TRAPEZE ADDITIONAL TIER (3 TIERS MAX) REFER TO DETAIL 18/S790 FOR CONN. TO STRUCTURE ABOVE UNISTRUT P1000 CHANNEL TRAPEZE SUPPORT NOTE: PROVIDE TRAPEZE SUPPORT OF CONDUIT BUS DUCT AND CABLE TRAY AT 8'-0" OC MAX SPACING AND AT BENDS AS REQUIRED NOTE: AT MULTI-LEVEL TRAPEZE, SEISMIC BRACING MAY BE AT EACH TIER, AS REQUIRED